Almost every motor that burns out on a site had an overload relay sitting right next to it. Either it was set wrong, it was the wrong type for the job, or someone turned it up to stop “nuisance tripping” the week before. A correctly set overload relay is the cheapest insurance a motor can have. Here is how it works, how to choose one, and how to set it so it protects the motor instead of just decorating the panel.
1. What an Overload Relay Does
A motor overload relay watches the current the motor draws and trips the starter if that current stays too high for too long. It sits after the contactor in a DOL or star-delta starter, and its auxiliary contact (the 95–96 normally-closed contact) is wired into the contactor coil circuit. When the relay trips, that contact opens, the contactor drops out and the motor stops.
The key word is time. A motor draws 6–8 times its full-load current for a few seconds every time it starts, and that is normal. What damages a motor is current that is only 10–50% too high but continues for minutes — enough to cook the winding insulation slowly. The overload relay is designed to ignore the short starting surge and act on the long, moderate overload.
2. What It Does NOT Do
An overload relay is not short-circuit protection. A short circuit produces thousands of amps in milliseconds; the relay is far too slow and will be destroyed long before it reacts. Short-circuit protection comes from the fuse, MCCB or MPCB upstream. Every motor feeder needs both: short-circuit protection for faults, overload protection for the motor.
3. The Three Types You Will Meet
4. Trip Class: How Fast It Trips
Trip class tells you the maximum time the relay takes to trip at 7.2 times its set current (IEC 60947-4-1):
| Trip class | Trips within (at 7.2× setting) | Use it for |
|---|---|---|
| Class 10 | 4–10 seconds | Standard duty: pumps, compressors, conveyors that start quickly |
| Class 20 | 6–20 seconds | Loads that take longer to accelerate: large fans, blowers, loaded conveyors |
| Class 30 | 9–30 seconds | Heavy-inertia starts: crushers, centrifuges, large ID fans |
Most thermal relays are Class 10. If a motor trips every time it starts even though running current is normal, the load is simply taking longer to reach speed than a Class 10 relay allows — the fix is a Class 20 or 30 relay (usually electronic), not a higher current setting.
5. How to Set It Correctly
6. Why an Overload Relay Keeps Tripping
A tripping relay is almost always telling the truth. Before touching the setting, check these, in this order:
7. The Mistake That Burns Motors
Turning the dial up until the tripping stops. The relay stops tripping because it has stopped protecting. The overload is still there — it is just cooking the winding silently now, and the next call is for a rewind or a new motor. If a relay trips, find the cause from the list above. If the setting genuinely has to go above nameplate current to keep running, the motor is undersized for the job and needs replacing with a larger frame, not a braver setting.
8. With a VFD or Soft Starter
A variable frequency drive has electronic motor overload protection built in. Enter the motor’s nameplate current in the drive’s motor parameters and the drive protects the motor itself; an external thermal relay is usually unnecessary for a single motor (and a thermal relay on a VFD output is unreliable anyway). Most soft starters also include motor overload protection with a selectable trip class, which suits heavy-inertia loads well.
9. Quick Checklist
Motor tripping and not sure whether it is the relay, the supply or the motor? Talk to us — share the nameplate and what the relay is set to, and we will help you find the real cause before it becomes a burnt winding.